环网柜

Ring Main Cabinet

Ring main cabinet is a group of transmission and distribution gas equipment installed in a metal or non-metallic insulated cabinet or made of assembled interval ring network power supply unit of electrical equipment, the core part takes circuit breaker, load switch and fuse. With advantages of simple structure, small size, low price, improve the safety of the power supply.

Product Parameters

serial numberParameter nameunit (of measure)parameter value
1rated voltagekV12
2Type of interrupter/vacuums
3Rated frequencyHz50
4rated currentA630
5Temperature rise test currentA1.1Ir
6Rated industrial frequency 1min withstand voltage (relative to earth)kV42
7Rated lightning impulse withstand voltage peak (1.2/50μs, relative to ground)kV75
8Rated short-circuit breaking currentkA20
9Rated short-circuit closing currentkA50
10Rated short-time withstand current and durationkA/s20/3
11Rated peak withstand currentkA50
12duration of ignition arcs≥0.5
13Number of openings under rated active load conditionssubstandard100
14Short-time frequency withstand voltage for auxiliary and control circuitskV2
15Power supplycontrol loopVDC48
auxiliary circuitVDC48
16service lifesurname Nian≥40
17protection classCabinet enclosure/IP4X
compartment/IP2X
18Gas rated pressure (20°C gauge pressure)MPa0.01
19Annual gas leakage rateV/V0.10%
20partial dischargepCWhole cabinet (1.1Ur) ≤20pC
Single insulator (1.1Ur) ≤ 5pC

Core Function

  • In terms of environmental performance, dry air does not have any impact on the environment at any stage of the product life cycle;
  • In terms of economy, customers do not have to invest in gas recovery at the end of the product life cycle, and there is no need for ventilation at the installation site of the equipment;
  • In terms of product reliability, dry air is characterized by a low risk of local release and a long service life.

Application Scenario

Widely used in urban residential districts, high-rise buildings, large public buildings, factories and enterprises and other load centers of the distribution station.