Pole mounted circuit breaker takes vacuum arc extinguishing and air insulation, able to carry, close and open load currents, overload currents and short-circuit currents in overhead distribution lines. The operating mechanism of the circuit breaker has electric spring and electric permanent magnet modes, and can be externally mounted with an error-proof interlocking function and an obvious disconnecting knife gate. The circuit breaker can be equipped with intelligent feeder terminal to realize the application of power distribution automation. It is suitable for contact point, section point, branch or user separate point of 10kV overhead distribution line.
| serial number | Parameter name | unit (of measure) | parameter value | |
| 1 | switching structure | Transformer form | / | Outside the sealing pole |
| insulating material | / | Epoxy resin covered with silicone rubber or outdoor epoxy resin | ||
| 2 | Dielectric | / | atmosphere | |
| 3 | rated voltage | kV | 12 | |
| 4 | rated current | A | 630 | |
| 6 | Rated cable charging and breaking current | A | 25 | |
| 7 | Rated short-circuit breaking current | kA | 20 | |
| 8 | Temperature rise test current | / | 1.1Ir | |
| 9 | Rated frequency 1min withstand voltage | Relative to/between | kV | 42 |
| intermittent | kV | 48 | ||
| 10 | Rated lightning impulse withstand voltage (1.2/50s) peak value | Relative to/between | kV | 75 |
| intermittent | kV | 85 | ||
| 11 | Rated short-time withstand current and duration | kA/s | 20/3 | |
| 12 | Rated peak withstand current | kA | 50 | |
| 13 | Rated short-circuit breaking current | kA | 20 | |
| 14 | Rated short-circuit closing current | kA | 50 | |
| 15 | Main circuit resistance | μΩ | ≤70 | |
| 16 | mechanical stability | substandard | ≥10000 | |
| 17 | Minimum creepage distance for external insulation | mm | 372 | |
| 18 | Rated short-circuit breaking current breaking times | substandard | ≥ 30 times | |
| 19 | Closing and opening not synchronized | ms | ≤2 | |
| 20 | Contact closing bounce time | ms | ≤2 | |
| 21 | Partial discharge (1.1Ur) | pC | ≤20 | |