Site-wide Search

Diversified Product Ecosystem Enhance Customer Experience

Products

一二次融合环网箱

Primary and Secondary Integrated Ring Main Unit

Primary and secondary integrated ring main cabinet (box) is the core of cable line fault rapid positioning self-healing solution, and also the key equipment for the current standardization, lean and intelligent construction of distribution networks.

Product Parameters

serial numberParameter nameunit (of measure)parameter value
"one" radical in Chinese characters (Kangxi radical 1)Common Parameters for Ring Network Cabinets
1Type of interrupter/vacuums
2Gas rated pressure (20°C gauge pressure)MPa0.01
stupid (Beijing dialect)Circuit Breaker Parameters
1Type of interrupter/vacuums
2Main circuit resistanceμΩ≤120
3Average speed of circuit breaker opening and closingSlotting speedm/s1.4±0.5
Closing speed1.1±0.5
4mechanical lifesubstandard≥10000 (vacuum)
surname SanDisconnect Switch Parameters
1rated currentA630
2Main circuit resistanceμΩIntegral to circuit breaker
4Voltage transformer and fuse parameters
1Type or model/Electromagnetic (three-phase five-column)
2Fuse type/spiral
3Fuse current ratingA1
4Rated short-circuit breaking current of fuseskA50
5Lightning arrester parameters
1Peak residual voltage under lightning surge current (5kA, 8/20μs)kV45/50
275% Leakage Current at 1mA DC Reference VoltagemA≤50*10-6
3continuous currentfull currentmA0.8
resistive currentmA≤200*10-6
6outer cabinet
1Housing Material/304 stainless steel
7DTU
1Analog input nominal valuephase currentA1 or 5
2Feeder automation functions /Centralized feeder automation function or distributed + centralized feeder automation function
3Backup power supply method /Maintenance-free valve regulated lead-acid batteries or supercapacitors or other new energy batteries

Core Function

  • Integrated design. Realize information collection and automation control. The station terminals and fault isolation devices are designed as a complete set, which can collect phase current, voltage, and zero sequence current and zero sequence voltage, and combine with the distribution automation system through fiber optic/wireless communication to realize data collection, parameter setting, and remote control of the line.
  • Cabinet flexible configuration, supporting full circuit breaker configuration, full load switch configuration, inlet load switch outlet circuit breaker and other configuration programs to meet customer requirements.
  • Safe and reliable, the switching device and main busbar are completely sealed in the fully insulated steel structure box, the cabinet structure is very compact. Anti-skidding shell can be installed with common padlock to ensure maximum operational safety.
  • Maintenance-free design. Blowing type arc extinguishing design to minimize contact wear, in the factory inflatable encapsulation is completed, the site does not require more installation and commissioning, the design of the primary equipment maintenance-free life of up to 30 years or more.

Application Scenario

Primary and secondary integrated ring main cabinets have been widely used in upgrading and new construction of distribution networks in urban and industrial areas.